Rheem 3.5 Ton Heat Pump Condenser (RP15AY42AD2NA)
The Rheem RP15AY42AD2NA is a Endeavor Line Classic Plus Series RP15AY heat pump outdoor unit built for 460 volt 3-phase power, the service found in many light commercial buildings, multifamily properties and offices. It is the outdoor half of a split system and must be paired with a matched R-454B indoor air handler; the AHRI-certified matches are listed below.
Performance
- Nominal capacity: 3.5 ton
- Compressor: Scroll, 2-stage (RLA 5.8 A, LRA 60.0 A)
- Refrigerant: R-454B (A2L)
- Sound rating: 74 dB
- Defrost: Demand defrost control with reversing valve for heating mode
AHRI-certified matched systems
Ratings below are from the AHRI Directory for this outdoor model with Rheem RH2TY air handlers. Each RH2TY rating covers both the 208/230V single-phase (J) and 460V three-phase (D) air handler versions.
| Matched air handler | Cooling BTU/h | SEER2 | EER2 | HSPF2 | AHRI ref. |
|---|---|---|---|---|---|
| RH2TY4821STANN | 40,000 | 14.3 | 9.0 | 7.5 | 216011652 |
| RH2TY4824STANN | 40,000 | 14.3 | 11.7 | 7.5 | 216581212 |
Electrical and connections
- Power supply: 460V 3-Phase, 60 Hz
- Minimum circuit ampacity: 9 A
- Maximum overcurrent protection: 15 A
- Outdoor fan FLA: 0.8 A
- Liquid line: 3/8"
- Suction line: 7/8"
Dimensions
- Height: 39.0 in
- Width x depth: 35.75 x 35.75 in
- Operating weight: 240 lb
- Shipping weight: 247 lb
Warranty
Rheem limited warranty applies per the Rheem warranty document for this series; terms differ for residential and commercial applications and require registration where stated.