Description
Sunstar SIU Vacuum U-Tube Tough Guy Heater | SIU50-20-TG-N5
The Sunstar SIU50-20-TG-N5 is a 50,000 BTU/hr natural gas infrared tube heater with 20 feet of radiant emitter folded into a U-tube, so the heater itself is only about 12' 9" long. It is part of Sunstar’s SIU vacuum U-tube Tough Guy line, built for warehouses, maintenance shops, loading docks, fire stations and other high-ceiling spaces where doors open often and heated air is lost the moment they do.
SIS and SIU heaters are vacuum (negative pressure) designs: a draft inducer at the exhaust end pulls combustion through the tube, so if a joint ever opens, room air is drawn in instead of combustion gas escaping. A heavy cast iron burner lights by direct spark with 100% gas shut-off, and a 30-second pre-purge and air proving switch confirm venting before gas flows.
With the firing leg running beside the cooler return leg, a U-tube spreads its heat more evenly than a straight tube of the same length, which makes it the go-to choice for spot heating a bay, work cell or dock door.
It has a single-stage gas valve and can be run from a line voltage or 24V thermostat, or switched on and off manually.
The Tough Guy option means every emitter tube is heat-treated aluminized steel, the construction Sunstar recommends for car washes, dairy barns, greenhouses, pools, wastewater plants and other humid or corrosive spaces.
For planning, mount it at least 11 feet above the floor when level or 10 feet when tilted 45 degrees, and keep 40 inches clear below it and 24 inches to the sides. It can be vented on its own, common vented with other heaters, or run indirect vented with building exhaust, and it can draw outside combustion air through its fresh air collar in dusty or humid buildings. Installation must be done by a licensed contractor to the manufacturer’s instructions and local codes.
Key Features
- 50,000 BTU/hr natural gas input
- 20' U-tube all-aluminized Tough Guy emitter, about 12' 9" overall
- Vacuum design pulls combustion through the tube for added safety
- Direct spark ignition with 100% gas shut-off
Frequently Asked Questions
How high should the SIU50-20-TG-N5 be mounted?
Sunstar lists a minimum of 11 feet above the floor with the heater level and 10 feet at a 45-degree tilt. Mount it as high as the space allows for even coverage; going below the minimum can make the area right underneath uncomfortably hot.
What clearance does it need from combustibles?
Keep at least 40 inches below the heater and 24 inches to the sides clear of anything that can burn, including stacked materials and vehicles parked underneath. The full clearance chart, including ceiling and end distances, is in the installation manual.
Can I convert it to propane?
Conversion requires the Sunstar factory kit for this exact model, installed by a qualified technician, so the simplest route is to order the heater for the gas you have.
What controls can I use?
A line voltage or 24V thermostat, a 24V thermostat with a relay kit, or a simple on/off switch. One thermostat can run several heaters within its rated load, or more with relay kits.