Description
Product Summary
The Bohn BEL0295AS6AMAB0405 is a 29,500 BTU/h nominal low profile walk-in unit cooler from the Bohn BEL Low Profile series, built for walk-in coolers in restaurants, convenience stores, grocery and food service. It uses air defrost, 5 fan 2-Speed EC fan motors and a 6 FPI coil, and runs on 115V 1-Phase power.
Heatcraft rates this model at 30,700 BTU/h with R-448A (10°F TD, 25°F SST), moving 3,050 CFM. It is approved for R-404A, R-448A, R-449A and ships with option package B0405 (factory-mounted TXV, liquid line solenoid valve and electronic thermostat (R-448A/R-449A)).
Key Features
- Low Profile design: Low-height cabinet saves headroom in walk-in boxes.
- Air Defrost: Off-cycle air defrost for coolers above freezing.
- 2-Speed EC fan motors: Energy-efficient EC motors reduce operating cost.
- 6 FPI coil: Fin spacing selected for the temperature application and defrost performance.
- Refrigerant flexibility: Rated for R-404A, R-448A, R-449A.
- Factory configuration: Factory-mounted TXV, liquid line solenoid valve and electronic thermostat (R-448A/R-449A).
Specifications
| Brand | Bohn |
|---|---|
| Model | BEL0295AS6AMAB0405 |
| Series | BEL Low Profile |
| Product Type | Low Profile Unit Cooler |
| Nominal Capacity (model designation) | 29,500 BTU/h |
| Capacity, R-404A (10°F TD, 25°F SST) | 26,000 BTU/h |
| Capacity, R-407A (10°F TD, 25°F SST) | 30,700 BTU/h |
| Capacity, R-407C (10°F TD, 25°F SST) | 30,700 BTU/h |
| Capacity, R-407F (10°F TD, 25°F SST) | 30,700 BTU/h |
| Capacity, R-448A (10°F TD, 25°F SST) | 30,700 BTU/h |
| Capacity, R-449A (10°F TD, 25°F SST) | 30,700 BTU/h |
| Capacity, R-507A (10°F TD, 25°F SST) | 26,000 BTU/h |
| Application | Cooler / medium temp |
| Defrost Type | Air Defrost |
| Fan Motor | 2-Speed EC (1/20 HP each) |
| Number of Fans | 5 |
| Airflow | 3,050 CFM |
| Fins Per Inch | 6 |
| Voltage | 115/1/60 |
| Unit MCA | 4.7 A |
| Unit MOPD | 20 A |
| Factory Option Package | B0405 (factory-mounted TXV, liquid line solenoid valve and electronic thermostat (R-448A/R-449A)) |
| Dimensions (H x D x L) | 16.4375 x 13.25 x 93.5 in |
| Estimated Net Weight | 115 lb |
Ideal Applications
- Walk-in coolers
- Restaurant and commercial kitchen coolers
- Floral and produce coolers
- Convenience store and grocery back rooms
- Beverage and dairy storage
Frequently Asked Questions
What refrigerants can the BEL0295AS6AMAB0405 use?
Heatcraft lists it for R-404A, R-448A, R-449A. Confirm the refrigerant matches your condensing unit and the expansion valve selected.
What voltage does the BEL0295AS6AMAB0405 require?
This unit cooler is wired for 115V 1-Phase (voltage code A). Provide a dedicated circuit sized to the nameplate MCA and MOPD.
Is the BEL0295AS6AMAB0405 for a cooler or a freezer?
It is an air-defrost unit for coolers held above about 34°F; it is not for freezer duty.
What condensing unit matches this evaporator?
Match the condensing unit capacity to the evaporator at your design suction temperature. Bohn BCH medium temp condensing units are a common pairing; HVAC365 can help size the system.
What is included?
The unit cooler ships with option package B0405 (factory-mounted TXV, liquid line solenoid valve and electronic thermostat (R-448A/R-449A)). Expansion valve, solenoid and controls are field supplied unless the option package includes them.
Why Buy From HVAC365
HVAC365 supplies Bohn and Heatcraft commercial refrigeration equipment to contractors, facility managers and business owners with competitive pricing, fast shipping and support from HVAC specialists. Contact HVAC365 for help sizing your walk-in load, confirming refrigerant and voltage, or matching this unit cooler with the right Bohn condensing unit, expansion valve and controls.