Description
The Bosch CL024-2HZC-AREPDA is a 2-ton horizontal water-to-air heat pump from the CL Series, Bosch's commercial line for water loop and geothermal buildings. Units like this are the workhorse of apartment buildings, hotels, condos and office floors: one heat pump per zone, hung above the ceiling, all tied to a shared building water loop with a boiler and cooling tower (or a ground loop). This model runs on 277V single-phase power, takes return air on the right end, discharges supply air out the opposite end, and has its water connections on the front-right of the cabinet.
Why a horizontal water source heat pump
Horizontal units are built for buildings where floor space is worth more than ceiling space. At 21.5" wide, 44" long and 18" tall, this cabinet fits above a dropped ceiling or in a soffit and leaves closets and mechanical rooms free. Because the compressor, coils and blower are all inside the one cabinet, there is no outdoor unit and no refrigerant line set to run, and each unit can be serviced or replaced without touching the rest of the system.
Picking the return side matters. On this right-return model, the filter rack and return air opening are on the right end when you face the control panel, and supply air leaves from the left end. Match it to your existing return duct and service access so you are not fighting the layout in the ceiling.
Rated performance
Bosch rates the CL Series to AHRI/ISO 13256-1 at all three standard application points. The numbers below are for this size with a copper water coil at 800 CFM and 6 GPM.
| Rating point | Cooling (BTU/h) | EER | Heating (BTU/h) | COP |
|---|---|---|---|---|
| Water Loop (86°F cooling / 68°F heating) | 24,200 | 14.0 | 28,300 | 4.7 |
| Ground Water (59°F / 50°F) | 26,850 | 19.5 | 22,650 | 4.4 |
| Ground Loop (77°F / 32°F) | 24,550 | 14.7 | 18,500 | 3.6 |
Use the water loop rating for a building loop held roughly between 60°F and 90°F. The ground water and ground loop ratings apply to open-well and closed geothermal systems.
Water coil
This unit uses a copper coaxial water coil, the standard choice for closed systems: building water loops with a cooling tower or fluid cooler, and closed geothermal ground loops filled with treated water or antifreeze. For open-loop well water, choose a cupro-nickel version instead.
Construction
- R-454B refrigerant, the low-GWP replacement for R-410A
- Coaxial copper water-to-refrigerant heat exchanger
- DuoGuard coated air coil for added corrosion resistance
- G90 galvanized steel cabinet lined with 1/2" 1.5 lb dual-density fiberglass insulation to keep noise and cabinet sweating down
- PSC blower motor with multiple speed taps for airflow setup
- 3/4" FPT water connections on the front-right, 3/4" FPT condensate drain
- Filter rack for a 17 x 25 filter on the return end
Electrical
| Power supply | 277V single-phase, 60 Hz |
|---|---|
| Minimum circuit ampacity (MCA) | 11.1 A |
| Maximum overcurrent protection (MOP) | 15 A |
Specifications
| Model | CL024-2HZC-AREPDA |
|---|---|
| Bosch part number | 7734026189 |
| Series | CL Series (commercial) |
| Nominal capacity | 2 ton |
| Configuration | Horizontal, right return, end discharge |
| Refrigerant | R-454B |
| Airflow | 800 CFM |
| Rated water flow | 6 GPM |
| Water coil | Copper coaxial |
| Blower motor | PSC |
| Unit dimensions (W x L x H) | 21.5" x 44" x 18" |
| Filter size | 17 x 25" |
| Shipping weight | 212 lb |
Before you install
Size the loop pump and piping for the rated 6 GPM, and use flexible hoses at the water connections so pump and compressor vibration does not carry into the building piping. Hang the unit on vibration isolators, pitch it slightly toward the condensate drain, and leave clear access to the control panel and filter. R-454B is an A2L (mildly flammable) refrigerant, so installation and service should be done by a technician trained on A2L refrigerants and your local code.