Description
Rheem Economizer With Single Enthalpy (Downflow) | RXRD-11MDDAM3
The Rheem RXRD-11MDDAM3 is an economizer with single enthalpy (downflow) for Rheem R-454B packaged rooftop units. It brings in outdoor air for free cooling when conditions allow and holds the code-required ventilation minimum the rest of the time.
Compatibility
- Rheem RACDYB cooling-only 7.5-12.5 ton (downflow)
- Rheem RGEDYB gas/electric 7.5-12.5 ton (downflow)
- Rheem RHPDYB heat pump 7.5-10 ton (downflow)
- Match the accessory to the unit cabinet and airflow direction; confirm against the Rheem accessory table for your exact model number.
Specifications
- Model: RXRD-11MDDAM3
- Modulation: Fully modulating 0-100% outdoor air
- Actuator: Gear-driven direct-drive
- Dampers: Ultra-low-leak; meets CA Title 24 and ASHRAE 90.1-2022
- Relief: Barometric relief damper standard
- CO2 / DCV: CO2 sensor input available (RXRX-AR02 wall sensor)
- Outdoor air hood: Field-assembled hood ships with economizer
- Power exhaust: Field-installed power exhaust option available
- Cabinet: D
- Controller: Siemens Climatix ECO (non-DDC; convertible to DDC with RXRX-DDC01)
- Changeover sensing: Single enthalpy; dual enthalpy via PD555460 sensor
- Manufactured by: MicroMetl
- Factory install: Yes
- Shipping weight: 86 lb
- Installed weight: 57 lb