Description
The MRCOOL MVPHK20 is a 20 kW electric heat kit for VersaPro 2nd Gen and Hyper Heat 2nd Gen MUAH air handlers on R-454B systems. It adds roughly 68,240 BTU/h of electric heat (calculated from its kW rating) for supplemental heat on the coldest days, emergency heat if the heat pump is down, and heat during defrost.
The kit slides into the air handler cabinet on support rails and plugs into the control board, and it carries its own built-in circuit breaker protection (2 circuit breakers). It runs on 208/230V single phase.
Compatibility
MRCOOL approves this kit for these air handlers: MVP-36-HP-MUAH-230A00-O, MVP-48-HP-MUAH-230A00-O, MVP-60-HP-MUAH-230A00-O. Check the air handler model before ordering, since smaller cabinets do not accept the larger kits.
Electrical
Number of Circuit Breakers: 2. Number of Relays: 4. Circuit 1 Heater Amps (208/230V): 36.0/40.0 A. Circuit 1 MCA (208/230V): 46.0/53.0 A. Circuit 1 MOP (208/230V): 50.0/60.0 A. Circuit 2 Heater Amps (208/230V): 36.0/40.0 A. Circuit 2 MCA (208/230V): 46.0/53.0 A. Circuit 2 MOP (208/230V): 50.0/60.0 A.
Key Features
- Built-in breaker: Circuit breaker protection built into the kit
- Slide-in design: Installs on rails inside the air handler cabinet
- Staged heat: Works with W1/W2 heat stages on a 24V thermostat
- R-454B systems: Made for VersaPro and Hyper Heat 2nd Gen air handlers
Frequently Asked Questions
Which air handlers does it fit?
MVP-36-HP-MUAH-230A00-O, MVP-48-HP-MUAH-230A00-O, MVP-60-HP-MUAH-230A00-O.
How much heat does it add?
20 kW, which works out to about 68,240 BTU/h.
Does it need its own circuit?
Yes. The heat kit is fed from its own 208/230V supply, sized to the MCA and MOP listed above.
Who should install it?
A qualified HVAC technician or electrician, following the air handler wiring diagram and local electrical code.