Description
Rheem 10 Ton Commercial Heat Pump Split System (RPCY2120DAZ + RHCYP2120DAS)
This AHRI-certified Rheem Commercial Classic split system pairs the RPCY2120DAZ heat pump outdoor unit with the RHCYP2120DAS belt-drive VFD heat pump air handler, both 460V 3-Phase, for light commercial buildings that need the air handler indoors in a mechanical room, mezzanine or above-ceiling platform.
System performance (AHRI 340/360)
- AHRI reference number: 214437993
- Rated cooling capacity: 114,000 BTU/h
- Efficiency: 11.0 EER, 14.1 IEER
- Refrigerant: R-454B (A2L)
- Heating at 47°F: 108,000 BTU/h, COP 3.4
- Heating at 17°F: 57,000 BTU/h, COP 2.25
Heat pump: RPCY2120DAZ
- Compressor: 1 scroll, 2-stage (RLA 14 A, LRA 123 A)
- Power supply: 460V 3-Phase, 60 Hz
- MCA / overcurrent protection: 24 A / 30/35 A (min/max)
- Sound rating: 88 dB (AHRI 270)
- Dimensions: 44 H x 74-17/63 L x 40 W in
- Weight: 642 lb operating / 662 lb shipping
Air handler: RHCYP2120DAS
- Blower: S = medium static; belt (adjustable) with standard VFD; 1725 rpm motor
- Motor HP by drive (R/S/T): 2 / 2 / 3
- Coil: 3 rows / 18 FPI / 16.5 sq ft face, louvered fin, 0.375 in rifled tube
- Metering: TXV field adjustable
- Configuration: Convertible vertical upflow / horizontal sideflow
- Refrigerant connections: 5/8" liquid, 1-3/8" vapor
- Filters: 1 x 16x25 or 2 x 16x25 (MERV 8/13 accessory, p.3)
- Dimensions: W 60.37 x H 35.10 x L 78.33 in
Electric heat
Rheem's RHCYP spec sheet lists auxiliary heater kits for the 7.5-ton RHCYP2090 only; no electric heat kit is approved for the 10-ton RHCYP2120.
Warranty
Rheem limited warranty for commercial applications: 5-year compressor and 1-year parts on each component. Full terms are in the Rheem warranty documents for the RPCY and RHCYP series.
White Paper